Page 117 - Tussen binnenstad en spoor - Leuven 2003
P. 117
115
The climate control and lighting systems are and a limited floor cooling system, a climate is cre- Air treatment is limited to fresh airflows required to
consequently divided into small control zones. ated in the atrium in which the comfort tempera- realise the requested indoor air quality. The energy
Heating and cooling are provided by hydronic ture in the occupancy zone during working hours required for the distribution of heat, cold and fresh
cooling ceilings with a maximum cooling capacity does not exceed 25°C over more than 150 working air is limited in this way together with the optimisa-
of 60 W/m2. For areas with higher cooling loads hours per annum and 28°C over more than 35 tion of the SFP-value (specific fan power) and good
the cooling ceiling is supplemented by floor working hours per annum. These design interven- pump controls. High return regenerative accumula-
ventilo-convectors. tions mean that the atria are unsuitable as a per- tors are used for heat recovery in the air handling
manent workplace: they do not fulfil the thermal units for the office floors. The results of the analysis
The conference rooms for mixed use and the and acoustic comfort requirements at all times. are incorporated in the specifications for the instal-
restaurant are used very intermittently. They are The addition of the glass interior façade and the lation components.
clearly spatially defined and cannot easily be natural ventilation possibilities are passive comfort
moved to another part of the building due to the measures that ensure that the atria can be used PROCESS-LINKED ENERGY CONSUMPTION The
technical provisions. For these functions the con- during the majority of the year for less formal or building owner’s IT-team was supported in formu-
trols for the cooling, heating and ventilating equip- demanding functions. The passive comfort meas- lating the energy aspects of the office equipment
ment are designed so that the periods of use and ures and the surrendering of the office functionality (central and distributed network infrastructure,
the number of users can be optimally anticipated. on the coldest and hottest days do ensure that the servers, telecommunications equipment and PCs).
primary energy consumption of the building (in A correct estimate of the heat load from office
The atria are conceived as buffer zones in which no energy performance terminology) is 17% lower equipment taking the uncertainty of future devel-
permanent workplaces are located. The climate in than would be the case with full air conditioning in opments in information technology into account, is
the atria is only roughly conditioned: the atria. an important aspect for the functional sustainability
- at low winter outside temperatures the atria are of the building.
heated up to 16°C by means of a floor heating BUILDING ENVELOPE The width/height-propor-
system. Draught along the vertical glazing is lim- tions of the atria are a compromise between ENERGY PERFORMANCE At the beginning of the
ited. On the railway side this is realised by pro- increasing the daylight availability and limiting the design the target value for the EPC-figure was 1.5
viding glass balustrades on each level on the heat-loss area of the atria. Despite the high per- (NEN 2916). This corresponds with the maximum
gangways. A glass interior façade is provided on centage of glazing, and despite the increased loss value for new office buildings recently imposed in
the ring road side. of heat through the floor over the bicycle parking the Netherlands. The EPC-figure for the prelimi-
- during hot sunny periods the inside temperature rack at external climate conditions, the building nary design of the building is 1.7.
in the atria is limited through solar blinds on all achieves a K40 (NBN B62-301) general level of heat Three elements form the basis for this limited sur-
glazing panes and by means of intensive natural insulation. passing of the target value:
ventilation with outside air. This means that both - the fresh airflow is 60 m3/(h. person), which is 50%
the vertical windows on the ring road side (at the THERMAL ASPECTS OF THE HVAC EQUIPMENT
atrium floor level) and the horizontal sliding win- Heat generation is realised by two preferential higher than normal in standard offices;
dows in the atrium roof are opened. A control condenser gas boilers with a 900 kW capacity, - the high glazing percentage of the façade;
algorithm was developed to adjust the opening and a non-preferential high return 1750 kW low - the application of seasonal thermal storage in the
angle of the vertical windows and the width of the temperature boiler. Cold generation is realised
opening in the atrium roof so as to obtain the through three refrigeration compressors (total ground was not financially and technically fea-
optimal ventilation rate in function of the inside capacity 4 MW, including cooling equipment sible.
and outside temperature. Opening the windows for the IT-infrastructure) that supply ice water at
does mean that noise pollution enters the atrium. a higher temperature to the cooling ceilings, Our experience has shown that the EPC-figure in
The natural ventilation is also accompanied by and ice water at a lower temperature to the Flemish building practice fluctuates between 1.8
uncomfortably high airflow speeds near the vertical ventilo-convectors. The cooling towers are used and 2.2.
windows. To limit noise pollution and draughts during appropriate weather conditions to act
insofar as possible a glass interior façade is placed as high-temperature coolers for the climate ceilings
(also see winter situation) at the vertical windows. without the intervention of the refrigeration
Thanks to the natural ventilation, the solar blinds compressors.